Gas Unit Heater Not Working? What GTA Warehouse and Property Managers Should Check First

The first hard frost hits and the shipping crew is working in their coats. The heater hanging over the dock door is silent, or its fan is running and blowing cold air. Out in the shop or the parking garage, another one comes on for a minute and then quits.
Gas unit heaters are the workhorses of GTA warehouses, loading docks, workshops and garages. They are simple machines, so a gas unit heater not working usually comes down to a short list of causes. Some you can rule out from the floor in a few minutes. The rest need a technician and, in most buildings, a lift. Here is how to tell the difference.
First, When to Stop and Get Help
You smell gas. Don't touch switches or try to restart anything. Get people out, then call your gas utility's emergency line or 911 from outside.
A carbon monoxide alarm is sounding, or staff report headaches, dizziness or nausea that ease when they step outside. Get everyone out and call 911.
You see soot, scorch marks or a lazy yellow flame. Leave the heater off and call for service.
It keeps tripping. Safety controls shut a heater down for a reason. If a breaker or reset trips again, stop resetting it.
The checks below stay on the floor and outside the heater on purpose. In Ontario, work on gas equipment has to be done by a certified gas technician. Unit heaters also hang 10 to 25 feet up, so climbing to one on a ladder between racking is a safety risk of its own.
Five Checks You Can Make Before Calling
The thermostat. Is it set above the room temperature and switched to heat? Warehouse thermostats get bumped, turned down for the summer, or knocked off the wall by forklifts. If it's in a locked guard, check that someone didn't leave it at the summer setting.
The service switch and breaker. Most unit heaters have a disconnect switch on or near the heater, and it's often turned off for the summer and forgotten. Check it and the panel. Reset a tripped breaker once at most.
One heater or all of them. One heater out points to that heater. Several out at once points to the gas supply, a shared circuit or the controls.
Recent work. Has anyone worked on the gas line, the roof or the electrical? A gas shutoff left closed is a simple fix, but have your technician or the contractor who closed it turn it back on.
The doors. If the heater is running and the space still won't warm up, look at how long the overhead doors are open. A heater sized for a closed dock can't keep up with a door that stays up all shift. That isn't a breakdown, but it's worth raising with your contractor.
Gas Unit Heater Not Working? The Usual Causes
A modern gas unit heater lights in a set order, much like a rooftop unit: the venter motor starts and is proven, the igniter fires, the gas valve opens and a sensor confirms the flame. Then the fan comes on to blow the heat down. If a step fails, the control stops and may lock out. These are the usual reasons:
Blocked vent. After a summer off, bird nests and debris in the vent cap are a common find. The pressure switch won't prove the venting, so the heater never tries to light.
Failed igniter or pilot. No ignition means no heat. Newer heaters retry a few times and lock out. Older heaters with a standing pilot stop when the pilot goes out or the thermocouple fails.
Dirty flame sensor or burners. Warehouse dust collects high up, right where the heater hangs. The burners light, then shut off seconds later because the control can't confirm the flame.
Fan problems. If the burners fire but the fan doesn't run, or runs slowly on worn bearings, the heat builds up and the high limit shuts the burners off. It shows up as heat that comes and goes, or a heater that is hot to look at but blows nothing.
Fan running, no heat. The fan is on but the burners aren't. Often a thermostat or wiring fault keeps the fan on, or the heater has locked out on one of the faults above.
Failed gas valve, control board or transformer. These need testing to confirm, so a technician rules out the simpler causes first.
Don't Skip the Heat Exchanger
Unit heaters burn gas inside the space people work in, so the heat exchanger is the only thing keeping combustion gases out of the room. Heat exchangers corrode faster around vehicle exhaust, road salt, and chemicals such as chlorine or solvents. When the heater is open for repair, ask the technician to inspect it. A cracked heat exchanger is a carbon monoxide risk and turns a repair into a replacement decision.
Also look at what's stored nearby. Pallets, cardboard and shrink-wrap stacked close to a heater are a fire risk. The manufacturer lists the clearances it needs, and they're easy to lose track of when racking gets rearranged.
What to Tell the Technician
With unit heaters, the right details often decide whether the problem is fixed on the first visit:
How high it hangs and what's underneath. Say whether a ladder will do or a scissor lift is needed, and whether racking or stock has to be moved. Arriving without the right lift is the most common reason a unit heater call takes two trips.
The make and model, if you can read the rating plate from the floor or have it on file.
What it's doing: completely dead, fan blowing cold, or heat that starts and stops.
When it stopped, and whether anything happened around then, such as a power outage or work on the building.
Access and hours: who can let the technician in, and when forklift traffic is quietest.
How to Avoid Unit Heater Breakdowns
Most unit heater failures can be caught before the cold arrives. Because the heaters are out of sight and out of reach, they're also the equipment most often left out of a fall start-up. A good annual service should include:
Cleaning the burners, fan and heat exchanger of dust.
Checking the igniter or pilot and the flame sensor.
Clearing and inspecting the vent, and testing the venter and pressure switch.
Testing the high limit and other safety controls.
Inspecting the heat exchanger and checking combustion.
Confirming the thermostat works and clearances to stored goods are kept.
Adding your unit heaters to a maintenance agreement puts this on a schedule, so the lift is booked once and every heater is done on the same visit.